Dixell XWEB 3000 Manual de Instruções Página 11

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 103
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 10
XWEB 500 – rel.1.0 –
2.1.2 SERIAL ADDRESS
The cable must have 2 or 3 wires with shield, minimum section 0,5mm
2
(eg. the BELDEN 8772).
From the XWEB 500 position the cable reaches all the instrument positions.
Do not execute loops or derivations:
Right connection
Wrong connection
Always keep the usb cable away from power cables.
Always keep the usb cable away from electro-magnetic or frequency sources.
Do not connect shield to ground.
Do not connect the “Gnd” terminal.
Remember to draw a map of the line. This will help you to find an error if something is wrong.
The instrument with RS485 have “+” and “- terminals, respect the polarity.
To keep the line balanced it is necessary a 100 Ohm resistor at the end of the line (you ca use the RS
485+ and RS 485- terminals of the last instrument connected).
10/01/2006- 1592010900 Pag. 11 / 103
Vista de página 10
1 2 ... 6 7 8 9 10 11 12 13 14 15 16 ... 102 103

Comentários a estes Manuais

Sem comentários